The XINJE XL5E-16T and XD5E-24R-E programmable logic...
High severity
Unreviewed
Published
Jan 15, 2025
to the GitHub Advisory Database
•
Updated Jan 17, 2025
Description
Published by the National Vulnerability Database
Jan 15, 2025
Published to the GitHub Advisory Database
Jan 15, 2025
Last updated
Jan 17, 2025
The XINJE XL5E-16T and XD5E-24R-E programmable logic controllers V3.5.3b-V3.7.2a have a vulnerability in handling Modbus messages. When a TCP connection is established with the above series of controllers within a local area network (LAN), sending a specific Modbus message to the controller can cause the PLC to crash, interrupting the normal operation of the programs running in the PLC. This results in the ERR indicator light turning on and the RUN indicator light turning off.